Valve design and manufacturing in Badalona since 1962

Pressure reducing valves

How do you adjust a pressure reducing valve?

How do you adjust a pressure reducing valve?
Article contents
  1. Basic guide to adjusting this type of valve
  2. Before you start: prerequisites for safe adjustment
  3. Step-by-step guide: the standard adjustment procedure
  4. Specifics by Valfonta model (M Series vs. PRV Series)
  5. Quick reference table: tools and direction of rotation
  6. Common problems during adjustment
  7. Frequently asked questions

Basic guide to adjusting this type of valve

Adjusting a pressure reducing valve is a simple but critical maintenance task.

The goal is to adjust the internal force of the mechanism so that the outlet pressure (“downstream”) remains stable at the desired value, regardless of inlet fluctuations.

The quick answer: On the vast majority of industrial valves, including the Valfonta M and PRV series, adjustment is achieved by changing the compression of the main spring with an adjusting screw or nut.

To do it correctly, you only need to remember this golden rule:

To raise the pressure (+): Turn the screw clockwise (to the right). This compresses the spring and exerts more force on the diaphragm or piston. Which one suits you? We cover it in our comparison of piston and diaphragm reducing valves.

To lower the pressure (-): Turn the screw counterclockwise (to the left). This decompresses the spring and reduces the opposing force.

Although the concept is simple, adjusting the valve safely and accurately requires a few essential preliminary steps, which we detail below.

Before you start: prerequisites for safe adjustment

It is not simply a matter of grabbing a wrench and turning. Before working on the valve, it is essential to make sure the installation meets certain minimum conditions so that the reading is accurate and the equipment is not damaged.

1. Pressure gauge installation (essential)

You cannot adjust what you cannot measure. For correct adjustment, you need visibility of what is happening inside the pipe. As our installation diagrams show, you need two pressure gauges:

Inlet pressure gauge: To verify that sufficient pressure is reaching the valve.

Outlet pressure gauge: This is the critical one. It must be located “downstream” of the valve so you can see in real time how the pressure changes as you turn the screw.

2. Cleaning and filtering

Before attempting to adjust a new or recently serviced valve, make sure the pipe is clean. A small metal chip or dirt lodged in the seat can prevent the valve from closing tightly, causing the pressure to rise uncontrollably and preventing fine adjustment. That is why we always recommend installing a Y-strainer immediately upstream of the reducing valve.

3. Avoid water hammer

Never adjust the valve by opening the flow all at once. The isolation valves (inlet and outlet) must be opened slowly. A sudden pressure change can damage the valve’s internal diaphragm or bellows before you even start adjusting.

Step-by-step guide: the standard adjustment procedure

Once the installation has been checked, we can proceed with the adjustment. This procedure applies to most of our spring-loaded self-operated valves.

Step 1: Relax the spring (recommended). If this is the first start-up, it is advisable to start with the valve “relaxed.” Turn the adjusting screw or nut counterclockwise until you feel that the spring is exerting hardly any pressure. This ensures that the valve is closed or at its minimum pressure point when flow starts.

Step 2: Open the flow slowly. Open the isolation valves (inlet and outlet) very slowly. This is vital to avoid water hammer, which could damage the valve internals. If the valve requires a condensate pot (for steam or fluids >125 °C), make sure it has been filled with water until it overflows before this step.

Step 3: Fine adjustment. With the fluid flowing (or with the valve static, depending on the process), start turning the adjusting element while closely watching the outlet pressure gauge.

  • To raise the pressure: Turn clockwise (right). In doing so, you are compressing the spring, which forces the valve to let more fluid through to balance that force.
  • To lower the pressure: Turn counterclockwise (left). Decompressing the spring reduces the setting.

Extra tip: If you need to lower the pressure and have overshot, it is sometimes more effective to “loosen” the screw a little more than necessary and then “tighten” it again until you reach the exact point from below. This helps seat the spring correctly.

Step 4: Verification. Once the desired pressure is reached on the gauge, lock the position (if the model has a locknut) and observe how the valve behaves when there is flow demand and when the demand is shut off.

Specifics by Valfonta model (M Series vs. PRV Series)

M Series (M1 and M2 industrial models)

These models are usually installed in larger-flow, larger-size applications.

M1 model: Adjustment is made by turning the adjusting nut located at the top, above the spring.

M2 model: It has a hex-head adjusting screw at the top of the tower.

Remember that, after adjustment, the outlet pressure acts directly on the diaphragm to compensate.

PRV Series (stainless steel valves)

This range has more compact or hygienic designs and in some cases requires specific tools:

PRV20 model: It is adjusted by turning the top adjusting nut.

PRV30 and PRV45 models: The design is more specific. To adjust the set point, you will need an 8 mm Allen key to turn the internal adjusting nut/screw.

PRV44 model: It uses a conventional adjusting screw located at the top of the cap.

Quick reference table: tools and direction of rotation

To make your job easier, we have compiled in this table exactly which tool you need for each model in our catalog and how to operate it.

Series / ModelAdjusting ElementUsual ToolTo raise pressure (+)To lower pressure (-)
M1 modelTop adjusting nut Open-end / adjustable wrenchClockwise (Compress) Counterclockwise
M2 modelAdjusting screw (Hex head) Open-end / adjustable wrenchClockwise (Compress) Counterclockwise
PRV20 modelTop adjusting nut Open-end wrenchClockwise (Compress) Counterclockwise
PRV30 modelInternal adjusting nut Allen key (8 mm) Clockwise (Compress)Counterclockwise
PRV44 modelTop adjusting screw Open-end wrenchClockwise (Compress)Counterclockwise
PRV45 modelInternal adjusting nut Allen key (8 mm) Clockwise (Compress) Counterclockwise

*Note: On all Valfonta models, the principle is universal: Compressing the spring (clockwise) always increases the set pressure.

Common problems during adjustment

1. The pressure rises by itself when I shut off the demand

If you set the valve to 3 bar with the tap open, but when you close it the pressure on the gauge starts to rise slowly until it equals the inlet pressure, you have a tightness problem.

Probable cause: Dirt or impurities lodged between the seat and the plug, preventing tight shutoff. It may also be due to a plug eroded by use.

Solution: Remove the cover, inspect the seat, and clean it or replace it if it is damaged. Remember: an upstream strainer is vital to prevent this.

2. The pressure fluctuates a lot (Instability)

If the gauge needle constantly rises and falls (cycling), adjustment is impossible.

Probable cause:

  • The control line tapping (if external) is too close to the valve, in a turbulent zone.
  • The valve is oversized for the actual flow passing through it.

Solution:

  • Make sure the pressure sensing point is at least 1 meter from the valve outlet.

Install a needle valve in the control line to “dampen” the signal and stabilize the reading.

3. I cannot reach the desired pressure

You turn the screw all the way, but the pressure does not rise enough, or you loosen it completely and the pressure is still too high.

Probable cause: The installed spring does not match the pressure range you need. Reducing valves work with different interchangeable springs to cover specific ranges (e.g., 1 to 8 bar, or 4 to 12 bar).

Solution: Check the valve nameplate to confirm the spring range (“RANGE”). If it is out of range, contact Valfonta to purchase the right spring.

You will find all models, with their pressure ranges and materials, on our pressure reducing valves page.

Need help from our technicians to adjust your valve?

Correct adjustment not only ensures that your process runs at the exact pressure required, but also extends the service life of the entire installation, protecting pipes, filters, and sensitive machinery.

Frequently asked questions

Should I adjust the valve with flow (dynamic) or without flow (static)?

 The general recommendation is to make the fine adjustment under dynamic conditions, that is, with a demand flow representative of your normal process. Reducing valves have a slight difference between the pressure at zero flow (lockup pressure) and the pressure with flow. If you set it under static conditions, the pressure may drop slightly below the desired value when you open the taps or machines “downstream.”

I have tightened the screw all the way and cannot reach the desired pressure. What is happening?

If you have reached the end of the screw’s travel and the outlet pressure is still low, do not force the mechanism. Most likely, the spring installed in your valve does not cover the range you need (for example, you have a 0.5-3 bar spring and need to reach 5 bar). You should contact Valfonta to purchase the right spring for your new operating range.

Why must the water seal pot be filled with water before adjusting on steam?

In applications with steam or fluids above 125°C, the water seal pot (condensate pot) acts as a thermal barrier. If you try to adjust the valve without first filling it with water until it overflows, the steam will come into direct contact with the actuator’s elastomeric diaphragm and can burn or deform it instantly, making adjustment impossible.

Does the mounting position affect adjustment accuracy?

Yes. Although models such as the PRV series allow some flexibility, the standard position (horizontal pipe, vertical actuator) ensures the best sensitivity and the least wear. Installing the valve with the actuator “lying down” (horizontal axis) is not recommended, as the weight of the internals and side friction can cause erratic adjustment or hysteresis.

What is the external control line for on models such as the M1?

The control line transmits the actual pressure in the outlet pipe to the diaphragm so that the valve “knows” when to close or open. On models that require an external line (such as the M1, or the M2 on steam), it is vital to connect it at least 1 meter from the outlet. If it is connected too close, fluid turbulence will distort the reading, causing the valve to oscillate and not regulate stably.

Does the valve need to be recalibrated over time?

 Self-operated valves are very stable and do not require continuous maintenance. However, springs may relax slightly after years of service or intensive cycling. We recommend checking the pressure on the outlet pressure gauge periodically and, if a deviation is observed, slightly retightening the adjusting screw to compensate.

Related valves

View all pressure reducing valves →

Related articles

Pressure reducing valvesWhere should a pressure reducing valve be installed?6 min read

Pressure reducing valvesWhat is a steam pressure reducing valve?14 min read

Pressure reducing valvesHow do you install a water pressure reducing valve?5 min read

Can we help with your installation?

Tell us the fluid, the inlet and outlet pressures, the temperature, and the flow rate, and we will recommend the right valve.

You can also call 933 720 888 or email valfonta@valfonta.com.